400 Hz AC LIGHT LOAD BANK – DIGITAL USB ALB-L-80DU
0 out of 5
Advantages
- Simple operation suitable for non-trained operators and personnel; no maintenance required
- Suitable for workshop or airside operation; silent unit rated at < 70 dB(A) at 7m / 23Ft
- Luggage type casing with pull up handle as standard for every lightweight load bank
- Cant protection – load bank works only when positioned on flat horizontal surface
- Digital load banks do not require any further calibration process once delivered
- Free DEKAL licensed software application and proper drivers included
- All measurements possible to archive and printout, including diagram graphics
- In accordance & fully complied with AFI 33-115 volume 2, Certified by: SAF/A6C
- 400 Hz AC 6-Pole receptacle in accordance with NATO & MIL-C-81790 specification
- Fine load regulation knob as standard for complete series of 400 Hz AC load banks
- Housing made of non-corrosive parts with component quality control by the manufacturer
- High reliability with multiple thermal protection – extremely resistant to high temperature
- Extra safety and isolated jack sockets for connecting external voltage measuring device
- Short worldwide delivery period with tracking feature and insurance for all products
- Spare parts availability and accurate on-time deliveries by appointed courier
- 2 years full warranty with extension option for all DEKAL load banks
- CE certification – health, safety, and environmental protection standards
- Made for GPU’s testing procedure according to ISO 6858, DFS 400, ARP 5015
- Classification CE marking, DIN, VDE, IEC, IP 21 protection rate level
- Customs classification Harmonized System tariff code HS: 8516808000
SKU: ALB-L-80DU
Category: DIGITAL USB - DU
400 Hz AC LIGHT LOAD BANK – DIGITAL USB ALB-L-80DU
- TECHNICAL SPECIFICATION
- MEASUREMENTS & INDICATIONS
- DIMENSIONS & WEIGHT
| TECHNICAL SPECIFICATION | ALB-L-80DU |
|---|---|
| VOLTAGE [V] * FREQUENCY [Hz] | 115 / 200 V AC ± 10 % * 400 Hz ± 10 % |
| LOAD / POWER [kW / kVA cosφ=1] | 0 – 80 kW ± 5 % |
| FINE ADJUSTMENT – POTENTIOMETER | 0 – 8 kW |
| RATE SWITCH REG. LOAD STEPS ± 5% ROUGH ADJUSTMENTS – 8 kW STEPS POWER [kW / kVA cosφ=1] |
9 SEQUENCE STEPS: 8 – 16 kW 16 – 24 kW 24 – 32 kW 32 – 40 kW 40 – 48 kW 48 – 56 kW 56 – 64 kW 64 – 72 kW 72 – 80 kW |
| FORCED AIR COOLING [m³/min & CFM] | 88.20 m³/min – 3120 CFM |
| MEASUREMENTS & INDICATIONS | |
|---|---|
| DIGITAL POWER METER PARAMETERS | 3 LINE HIGH BRIGHTNESS RED LED DISPLAY CLASS: ±0.5 % ; S ACC. IEC 62053-22:2003; DISPLAYED: V / A / Hz / cosφ=1 / kW / kVA; |
| USB INTERFACE SPECIFICATIONS | USB PLUG IN CONNECTION FOR DATA PRINTOUT ARCHIVE, INCLUDING FREE DEKAL LICENSED SOFTWARE & USB CABLE |
| LIGHT INDICATION | PHASE INDICATION, PHASE ROTATION, INTERLOCK CIRCUIT |
| GPU TESTING PROCEDURE* | *Proposal procedure: LOAD raising from 0 → 100% ? 30 seconds; HOLD at 100% ? 5 minutes; LOAD decrease from 100 → 0% ? 10 minutes |
| ENGINE DECARBONISING* | *Proposal procedure: LOAD raising from 0 → 100% ? 30 seconds; HOLD at 100% ? 45 minutes; LOAD decrease from 100 → 0% ? 15 minutes |
| DIMENSIONS & WEIGHT | |
|---|---|
| LOAD BANK SIZE [L x W x H] mm / Kg | 510 x 210 x 450 / 26 |
| LOAD BANK SIZE [L x W x H] In / Lbs | 20 x 8.3 x 17.7 / 57 |
| TRANSPORT CASING [L x W x H] mm / Kg | 630 x 600 x 330 / 9 |
| TRANSPORT CASING [L x W x H] In / Lbs | 24.8 x 23.6 x 13 / 19 |
| LOAD BANK PAINTING / TRANSPORT CASING | FINE POWDER COATING STRUCTURE DRYLAC® 29_80081 LIGHTWEIGHT LUGGAGE TYPE CASING WITH PULP UP HANDLE |